Rinnai Water Heater Leaking
A Rinnai tankless water heater can leak from several distinct locations — and identifying where the water originates is the first diagnostic step. Rinnai RUR and RUS condensing models produce a constant small flow of acidic condensate from the drain line that is normal, but a sudden increase in condensate flow, dripping at the heat exchanger body, or water at the gas components indicates a problem. The T&P (temperature and pressure) relief valve drips when system pressure rises above 150 PSI — common in closed plumbing systems without an expansion tank. The water inlet and outlet union fittings are a frequent leak source, especially after installation or any plumbing work. The internal flow sensor O-ring can fail over time. In freeze climates, Code 03 indicates the built-in freeze protection has activated — but if power was lost during freezing weather, the heat exchanger body may have cracked. This guide covers all Rinnai leak sources with specific procedures for each.
Try the AI Diagnosis ToolAI Repair Tools
Common Symptoms
- Water dripping from the bottom of the Rinnai unit
- Water pooling under the unit on the floor
- T&P relief valve dripping from the discharge pipe
- Water at the union fittings on the cold inlet or hot outlet connections
- Code 03 displayed — freeze protection activated
- Condensate drain line producing more water than usual
- Water seeping from the heat exchanger body (perforation from scale or freeze)
Most Likely Causes
- 1
Condensate Drain Line Leak (Normal Flow vs. Heat Exchanger Perforation)
Rinnai RUR and RUS condensing models produce acidic condensate (pH 3–5) during normal operation — a small, steady flow from the 1/2-inch flexible condensate drain tube is expected and not a leak. An abnormal increase in condensate volume, condensate dripping from the heat exchanger body rather than the drain tube, or water with a bluish or rust-colored tint from the drain indicates a more serious problem. Code 14 (thermal fuse trip from overheating) can precede a heat exchanger perforation on heavily scaled condensing units — scale creates localized hot spots that eventually erode the heat exchanger wall. A perforated heat exchanger allows water to contact the exhaust gas side, producing an acidic mist that drips from unexpected locations. Test: check if the 'condensate' is actually soapy or has a metallic smell — these indicate it is potable water from a perforation, not normal condensate. If perforation is confirmed, the heat exchanger must be replaced.
- 2
T&P Pressure Relief Valve Drip (Expansion Tank Required on Closed Systems)
The T&P (temperature and pressure) relief valve on a Rinnai tankless unit opens at 150 PSI or 210°F to prevent catastrophic overpressure. Intermittent dripping from the T&P discharge pipe in a system that has a check valve, pressure-reducing valve (PRV), or backflow preventer installed on the cold supply is almost always caused by thermal expansion pressure — not a failed valve. When water heats up and expands, the expansion has nowhere to go in a closed system, so pressure rises until the T&P opens. Fix: install a thermal expansion tank on the cold supply between the shutoff valve and the unit. After installing the expansion tank, if the T&P continues to drip, test the pressure with a gauge; above 80 PSI, adjust the PRV. Replace the T&P valve only if it drips at normal operating pressure after an expansion tank is installed.
- 3
Inlet/Outlet Union Fitting Leak (Teflon Tape + Pipe Dope Required)
Rinnai tankless water heaters use threaded union fittings on the cold water inlet and hot water outlet connections. These unions can weep at the threads if they were not sealed with both PTFE (Teflon) tape and pipe thread sealant (pipe dope) during installation, or if the unions were tightened and loosened during service and not re-sealed. A union leak is typically a slow drip that is worse when the unit has been running. Fix: shut off cold water supply, open a hot tap to depressurize, unscrew the leaking union, clean the male threads with a wire brush, wrap with 3–4 turns of PTFE tape clockwise on the threads, apply a thin coat of pipe dope over the tape, and re-tighten (hand-tight plus 1–2 turns with a wrench — do not over-torque the plastic union nut).
- 4
Flow Sensor O-Ring Failure
The cold water flow sensor inside the Rinnai unit contains an O-ring seal between the sensor body and the water manifold. Over time, the O-ring can degrade and allow water to seep past the sensor housing, producing a drip at the bottom of the unit that appears to come from the heat exchanger area. The leak is usually a slow weep rather than a stream, and may worsen as water pressure increases. Diagnosis: with the front panel removed, run the unit and watch the flow sensor body — a weep visible at the sensor housing confirms an O-ring failure. Fix: shut off water supply, remove the flow sensor (model-specific procedure — consult Rinnai service manual), replace the O-ring with an OEM-spec Rinnai part, lubricate with silicone grease, and reinstall.
- 5
Freeze Damage — Code 03 and Post-Freeze Inspection
Rinnai tankless units (all V, RU, RUR, RUS series) have built-in freeze protection circuits that circulate water through the heat exchanger using small electric heaters when ambient temperature drops near freezing. Code 03 indicates the freeze protection circuit is active or was activated — it is informational and clears when the unit warms up. However, the built-in freeze protection ONLY works when the unit has AC power. If power was lost (storm, tripped breaker) during a hard freeze, the heat exchanger may have cracked. Post-power-outage freeze inspection procedure: close the cold water isolation valve; open a hot tap to relieve any remaining pressure; slowly open the cold valve just enough to pressurize the unit; inspect all connections and the heat exchanger body for dripping or weeping. If the heat exchanger shows cracks or weeping after freeze exposure, the exchanger must be replaced — do not operate the unit.
- 6
Scale-Perforated Heat Exchanger on RUR/RUS (Descale vs. Replace Decision)
On Rinnai RUR and RUS condensing models with years of scale accumulation, the heat exchanger can develop pinholes or micro-fractures where scale-induced hot spots thinned the tube walls. This produces a characteristic leak: water appears inside the combustion/exhaust chamber rather than at plumbing fittings, and the condensate drain may carry potable-water volume far exceeding normal condensate production. Descaling at this stage rarely seals existing perforations — descale first to confirm the heat exchanger is not simply coated (a successfully descaled exchanger with no leaks visible is reusable), but if leak points are confirmed after descaling, the heat exchanger assembly requires replacement. Rinnai heat exchanger replacement is a significant repair ($400–$800 parts + labor) — compare against the unit's age and the 12-year residential warranty before proceeding.
Not sure if this is the right fix for your exact model?
Upload a photo of your appliance label — Fix-It Fast AI will identify your exact unit and tailor the diagnosis.
Quick DIY Checks
DANGER: If water is dripping onto the gas valve, igniter, or burner assembly from a heat exchanger perforation or union fitting leak, shut off the gas supply valve and the cold water supply valve immediately and do not operate the unit until the leak is repaired. Water and gas components are an ignition hazard.
WARNING: Do NOT remove the T&P valve to stop dripping — it is a critical safety device. A T&P that has been removed or disabled can allow catastrophic tank rupture or explosion if the unit overheats or overpressurizes.
CAUTION: Condensate from Rinnai RUR/RUS condensing models is acidic (pH 3–5). Wear nitrile gloves when working on the condensate drain line, neutralizer housing, or when wiping down water inside a condensing unit. Do not let condensate puddle on unsealed concrete.
CAUTION: If freeze damage is suspected, do not turn on the unit without completing the cold-supply pressurization inspection described in Step 5. Operating a Rinnai with a cracked heat exchanger risks water contact with gas components and potential combustion hazard.
- 1Step 1 — Identify the leak source precisely: remove the front cover and use a flashlight and dry paper towel to find exactly where water originates. Wipe all visible components dry, then run a hot water draw and watch under flow. Key locations: union fittings on cold inlet and hot outlet (threaded connections at the top of the unit), the T&P valve discharge pipe (usually a 3/4-inch pipe running to a drain), the flow sensor body on the cold side, the condensate drain port at the bottom of RUR/RUS units, and the heat exchanger body itself. Accurately locating the source before starting any repair prevents unnecessary disassembly.
- 2Step 2 — Repair a union fitting leak (Teflon tape + pipe dope): close the cold water supply valve and open a hot tap downstream to release pressure. Remove the leaking union fitting (cold inlet or hot outlet). Clean male threads with a wire brush to remove old sealant residue. Wrap 3–4 turns of PTFE (Teflon) tape clockwise around the threads, starting at the first thread. Apply a thin coat of pipe thread sealant (pipe dope) over the tape. Re-thread the union and tighten by hand, then one to two turns with a wrench. Do not over-torque plastic union nuts — hand-tight plus one full turn is sufficient. Restore water supply and check for drips under pressure for 5 minutes.
- 3Step 3 — Address T&P valve dripping (expansion tank): if the T&P valve drips intermittently — especially after a hot water draw — and the system has a check valve or PRV on the cold supply, the fix is an expansion tank. Install a potable-water thermal expansion tank on the cold supply between the shutoff valve and the unit (typically 2-gallon for tankless; a plumber should verify sizing based on supply pressure). Pre-charge the tank's air bladder to match cold supply pressure (typically 50–80 PSI) before installing. After installing the expansion tank, monitor the T&P for 48 hours — dripping should stop. If the T&P still drips, measure supply pressure with a gauge; above 80 PSI, reduce with the PRV.
Get the full fix — Pro members get unlimited AI diagnoses
Save your repair history, get step-by-step AI guidance on any water_heater issue, and avoid $150+ service call fees.
Try Pro — $7.99/mo- 4Step 4 — Replace the flow sensor O-ring: shut off cold water supply and unplug the unit. Remove the front cover and locate the flow sensor on the cold inlet manifold — it connects via a two-wire or three-wire electrical connector. Disconnect the wiring harness, remove the retention clip or screw holding the sensor, and slide the sensor out of the manifold. Identify the O-ring (a small ring seated in a groove on the sensor body or on the manifold port). Replace with an OEM Rinnai O-ring for your model (part number in the service manual) — do not use generic O-rings, which may not be rated for potable water temperature range. Lubricate the new O-ring with food-grade silicone grease. Reinstall the sensor, reconnect wiring, restore water supply, and check for leaks.
- 5Step 5 — Perform post-freeze inspection (Code 03 or after power outage in cold weather): if Code 03 appeared or if the unit lost power during below-freezing temperatures, inspect for freeze damage before restarting. Close the cold supply isolation valve. Open a hot tap to relieve pressure. Slowly crack open the cold supply valve just enough to pressurize the unit — do not open it fully. Inspect the heat exchanger body, all water connections, and the union fittings for any weeping or dripping while under pressure. If any leak appears from the heat exchanger body, close the cold supply immediately — a freeze-cracked heat exchanger must be replaced before the unit can be used. Do not operate a Rinnai with a cracked heat exchanger; water can contact the burner assembly.
- 6Step 6 — Evaluate a condensate leak on RUR/RUS (descale vs. replace): if water appears from the heat exchanger body on an RUR or RUS condensing model, first descale the unit by circulating white vinegar or CLR through the service port isolation valves for 60–90 minutes. After flushing and restoring operation, watch under a hot water draw for 5 minutes. If the leaking stops after descaling, the unit likely had a loose scale deposit blocking a very small weep point that is now visible but self-sealing after descale; monitor over the next few days. If the leak continues after descaling, the heat exchanger has a true perforation. At this point, compare the cost of heat exchanger replacement ($400–$800 parts + labor) against the unit's age — if older than 10 years or outside the 12-year warranty, replacement of the full unit may offer better long-term value.
Save $150+ on a single service call
Less than a cup of coffee — fix it yourself with expert guidance.
- ✓ Step-by-step repair guides with exact part numbers
- ✓ Expert diagnosis in seconds — 500+ problems covered
- ✓ Full tool list & cost estimate before you spend a dime
$150+ service call vs. $7.99/mo · Cancel anytime
Repair vs Replace
Most Rinnai leaks — union fittings, T&P valve drip from thermal expansion, flow sensor O-ring, condensate drain — are inexpensive to fix and do not indicate a fundamental unit failure. A freeze-cracked or scale-perforated heat exchanger is more serious. For units under the 12-year residential heat exchanger warranty, Rinnai may cover the repair; contact Rinnai technical support at 1-800-621-9419 before paying for a heat exchanger out-of-pocket. For older units outside warranty, compare repair cost against full replacement — on a unit older than 12 years, a full unit replacement may offer better ROI than a heat exchanger swap.
Est. Repair Cost
$0–$400 (union re-seal free, O-ring $10–$25, expansion tank $30–$80, heat exchanger replacement $400–$800 parts + labor)
Est. Replacement Cost
$900–$2,200 for a new Rinnai unit installed
Recommended Tools & Parts
- Buy on Amazon →
PTFE (Teflon) Tape and Pipe Thread Sealant (Pipe Dope)
Required for re-sealing Rinnai union fittings on cold inlet and hot outlet connections. Use both tape and paste-style pipe dope together — tape alone is insufficient for water connections that are repeatedly tightened. Do not use tape on flare or compression fittings.
$5–$15
- Buy on Amazon →
Thermal Expansion Tank (2-gallon, potable water rated)
Required for closed plumbing systems (those with a check valve, PRV, or backflow preventer) to prevent T&P valve dripping from thermal expansion pressure. Pre-charge to match cold supply pressure before installing. Verify sizing with a plumber for systems above 80 PSI.
$30–$80
- Buy on Amazon →
Rinnai Flow Sensor O-Ring Kit (model-specific)
OEM replacement O-ring for the Rinnai flow sensor body or manifold port. Fixes slow weep at the flow sensor housing. Use only OEM Rinnai spec — generic O-rings may not match the temperature and chemical resistance requirements. Check the part number in your unit's service manual.
$10–$25
- Buy on Amazon →
White Vinegar or CLR Calcium, Lime & Rust Remover (Descale Kit)
Descaling solution for Rinnai RUR/RUS condensing heat exchanger to address scale-related leaks. Use 3 gallons undiluted white vinegar or CLR, circulated via service port isolation valves and a submersible pump for 60–90 minutes. Required before replacing a suspected perforated heat exchanger to confirm the perforation is genuine.
$10–$25
Links are Amazon affiliate links (tag: fixitfastai-20). Prices are estimates.
Still stuck? Let AI take a look.
Describe your problem or upload a photo — get a diagnosis in seconds.
Related Repairs
Water Heater — No Hot Water
No hot water at all or only lukewarm? Start with the reset button — then check the heating element or pilot light.
Read guide →Water Heater Leaking — T&P Valve, Drain Valve, Anode Port & Tank Diagnosis
Puddle around your water heater? The leak location tells you whether it's a $10 fix or a tank replacement — T&P valve, drain valve, anode port, dielectric union, and bottom rust all diagnosed here.
Read guide →Water Heater Not Making Enough Hot Water: Causes and Fixes
Running out of hot water fast? Thermostat setting, sediment buildup, broken dip tube, heating element, or undersized tank — here's how to fix it.
Read guide →Water Heater Pilot Light Won't Stay Lit: Thermocouple Fix
Water heater pilot light keeps going out? A failed thermocouple is the #1 cause — a $15 part you can replace yourself in 30 minutes.
Read guide →Save $150+ on a single service call
Less than a cup of coffee — fix it yourself with expert guidance.
- ✓ Step-by-step repair guides with exact part numbers
- ✓ Expert diagnosis in seconds — 500+ problems covered
- ✓ Full tool list & cost estimate before you spend a dime
$150+ service call vs. $7.99/mo · Cancel anytime
Still not sure what's wrong?
Get an AI diagnosis in seconds — describe the problem or upload a photo.
Get an AI Diagnosis⚡ Get step-by-step help for YOUR specific appliance
Our AI diagnoses your exact model — not just generic advice. Upload a photo or describe the issue and get a repair plan in seconds.
No account needed for diagnosis. Cancel Pro anytime.
Related Tools
Frequently Asked Questions
- Why is my Rinnai T&P valve dripping and how do I stop it?
- A dripping T&P (temperature and pressure) relief valve on a Rinnai tankless unit almost always indicates thermal expansion pressure in a closed plumbing system — not a failed valve. If your cold supply has a check valve, pressure-reducing valve, or backflow preventer, heated water has nowhere to expand, so pressure rises until the T&P opens. Fix: install a 2-gallon thermal expansion tank on the cold supply (pre-charged to match your supply pressure). After installing the expansion tank, if the T&P still drips, measure your supply pressure — above 80 PSI, reduce it with the PRV. Do not remove or cap the T&P valve; it is a life-safety device.
- Is it normal for my Rinnai RUR or RUS to drip water from the bottom?
- Yes — a small, steady drip from the condensate drain port on the bottom of a Rinnai RUR or RUS condensing model is normal. These units extract heat from the exhaust stream, producing acidic condensate (pH 3–5) as a byproduct. The condensate exits via a 1/2-inch flexible drain tube at the bottom of the unit, typically routed to a nearby floor drain. If the drip volume suddenly increases, water appears from the heat exchanger body rather than the drain port, or the water has a metallic smell, that indicates a heat exchanger perforation that requires further diagnosis.
- What should I do if Rinnai Code 03 appears after a hard freeze?
- Code 03 on a Rinnai means the freeze protection circuit activated. If power remained on during the freeze, the built-in freeze protection likely prevented damage — Code 03 should clear when the unit warms up. However, if power was lost during freezing temperatures, inspect for freeze damage before restarting: close the cold supply valve, open a downstream hot tap to relieve pressure, then slowly crack the cold supply valve to pressurize the unit. Inspect all connections and the heat exchanger body for any weeping or dripping. If a leak appears from the heat exchanger body, close the cold supply and call for service — a cracked heat exchanger must be replaced before the unit can be safely operated.