Swollen AC Capacitor: Signs, Symptoms, and Replacement Guide
A swollen or bulging AC capacitor is the most common residential HVAC failure — in warm climates like Florida, Georgia, and Texas, run capacitors fail at rates that make them essentially a maintenance item after 5–7 years. The run capacitor assists the compressor and condenser fan motor on every start cycle and continuously while running; when it fails, the compressor either won't start, runs sluggishly and draws excess amps, or trips the breaker on startup. A start capacitor (present on hard-start kit installs, not all units) is only in the circuit during the first fraction of a second of startup. I've replaced thousands of capacitors in the field — the physical signs are unmistakable once you know what to look for, and a $20 replacement is almost always the right call when you see a dome or oil on the capacitor case. This guide covers run capacitors (the most common failure), start capacitors, the microfarad test procedure with expected values, and the critical safe discharge steps before you touch any terminal. For systems where the capacitor failure is causing the contactor to buzz or not pull in, see /fixes/contactor-buzzing-not-pulling-in. For a breaker that trips when the AC starts, see /fixes/breaker-trips-when-ac-starts. If the system still doesn't cool after replacing the capacitor, see /fixes/lennox-ac-not-cooling or /fixes/trane-ac-not-cooling. Use /wiring-scan to upload a photo of the capacitor for AI identification and specification lookup.
Try the AI Diagnosis ToolAI Repair Tools
Common Symptoms
- Outdoor unit compressor hums for 1–3 seconds then shuts off — thermal overload trip
- AC breaker trips immediately at startup — compressor drawing locked rotor amps without capacitor assistance
- Condenser fan starts but compressor won't start, or compressor starts but runs slowly
- System cools poorly — runs continuously but house temperature barely decreases
- Visible dome or bulge on the top of the cylindrical capacitor can
- Oil residue, dark fluid staining, or dried oil crust around the capacitor base or terminals
- Capacitor case discolored (brown, black) or visibly cracked
- High amp draw on the compressor — clamp meter reading above nameplate RLA when running
Most Likely Causes
- 1
Thermal Degradation — Heat Cycling Breaks Down Dielectric Film (Most Common)
AC run capacitors use polypropylene film as the dielectric between rolled aluminum foil conductors. Every start cycle and continuous operation at elevated temperatures degrades the film. Inside the condenser cabinet on a 95°F summer day, capacitor operating temperature reaches 140–165°F. Manufacturer ratings typically assume a maximum operating temperature of 70°C (158°F); sustained operation near or above this threshold halves capacitor life with each 10°C increase (Arrhenius rule). As the dielectric breaks down, the capacitor loses microfarad value and eventually shorts internally. Internal shorts cause gas generation inside the sealed can — the internal pressure is what causes the visible dome or bulge on the top of the case. A domed capacitor is a failed capacitor — replace immediately.
- 2
Overvoltage or Voltage Spikes — Dielectric Puncture
Capacitors are rated for a maximum working voltage (typically 370VAC or 440VAC for residential units). Voltage spikes from lightning, utility switching events, or a failing transformer can puncture the dielectric film at weak spots, creating a partial short. Partial dielectric failure reduces microfarad value without always causing the visible dome — this is the 'failed but not obviously failed' capacitor that shows up on a multimeter test as 20–25 µF on a 35 µF rated capacitor. Always use a 440VAC-rated capacitor as a replacement (even if the original was 370VAC) — the higher voltage rating provides a larger safety margin against voltage transients.
- 3
Age and Capacitor Chemistry — End of Service Life
Residential dry-film run capacitors have a typical service life of 5–10 years under normal conditions. After 8–10 years, microfarad value degradation to below the ±6% AHRI tolerance is expected even without visible physical damage. A capacitor that measures 29 µF on a 35 µF unit (17% low) will cause the compressor to run hotter and draw more amps on every cycle, accelerating compressor bearing wear. Proactive replacement at 8–10 years (or any time capacitance drops below 10% of rated value) extends compressor life by reducing thermal stress. The cost of proactive capacitor replacement ($20–$35) is orders of magnitude less than a compressor replacement ($800–$2,500).
- 4
Run vs. Start Capacitor — Different Failure Modes
The run capacitor is always present on a residential AC unit — it is a single cylindrical can (or dual-run can with three terminals: HERM for hermetic/compressor, FAN for condenser fan, C for common). It is in the circuit continuously during operation, not just at startup. The start capacitor (usually found only on hard-start kit installs like Supco SPP6 or MARS 32456) is a higher-microfarad, lower-duty-cycle component that is only in the circuit for 300–500 milliseconds at startup. A start capacitor is physically larger in MFD value (88–108 µF or 161–193 µF) and uses a potential relay to remove it from the circuit once the compressor reaches about 75% of running speed. Start capacitors fail differently — often an open circuit rather than a dome — and their failure shows as startup difficulty specifically (longer startup time, humming on first start of the day) rather than continuous running problems.
Not sure if this is the right fix for your exact model?
Upload a photo of your appliance label — Fix-It Fast AI will identify your exact unit and tailor the diagnosis.
Quick DIY Checks
AC run capacitors store a lethal electrical charge at voltages up to 600VDC even after the AC power has been removed. ALWAYS wait a minimum of 5 minutes after turning off the outdoor unit disconnect before touching capacitor terminals. After the waiting period, ALWAYS manually discharge the capacitor by short-circuiting HERM-to-C, FAN-to-C, and HERM-to-FAN with an insulated screwdriver, then verify discharge with a multimeter (should read less than 5VDC). A capacitor discharge through a human body causes ventricular fibrillation. Do not rush this step under any circumstances.
A capacitor with a visible dome, bulge, or oil leakage has built up internal pressure and may rupture. Do not attempt to measure or handle a visibly failed capacitor under power. Turn off the disconnect, wait 5 minutes, then discharge before removing. Do not attempt to 'drain' oil from a leaking capacitor or reassemble a damaged capacitor — replace it entirely. The internal dielectric oil from a leaking capacitor is an irritant; avoid skin contact and dispose of the failed capacitor per local regulations.
The outdoor unit disconnect and condenser cabinet line-side wiring carry 240VAC even when the thermostat is off. The capacitor terminals and contactor line-side are energized whenever the main breaker is on. Always verify the disconnect is pulled or switched to OFF and use a non-contact voltage tester to confirm de-energization before opening any panel or touching any component. The disconnect only de-energizes the load side — the line side (line-in wires to the disconnect) remain live at all times from the breaker panel.
- 1Visual inspection — identify capacitor condition before touching anything: Turn off the outdoor unit at the disconnect box. Open the side access panel of the condenser (4–6 screws). Locate the capacitor — a cylindrical aluminum can, typically 2–4 inches in diameter and 4–6 inches tall, with terminals on top and a wiring harness. Inspect the top of the can: a flat or slightly concave top is normal. A convex dome, bulge, or top that has lifted higher on one side than the other = the capacitor has internally gassed and is failed. Inspect the base and terminals for oil residue, dark staining, or crystallized deposits. Any visible dome, leak, or bulging = replace immediately, no further testing needed. If the capacitor looks physically normal, proceed to the electrical test.
- 2Safe discharge procedure — MANDATORY before touching terminals: Wait 5 minutes after removing power at the disconnect for passive discharge through the bleed resistor (most modern capacitors have a 15k–20kΩ bleed resistor that discharges them within 1–2 minutes, but confirm by testing). After 5 minutes, hold an insulated-handle screwdriver by the plastic handle only. Touch the metal blade of the screwdriver across the HERM and C terminals simultaneously — a small spark may occur, which is normal. Then bridge the FAN and C terminals the same way. Then bridge HERM and FAN. After all three pairs have been shorted, the capacitor is fully discharged. Verify by setting your multimeter to DC voltage mode and measuring across HERM-to-C — it should read less than 5VDC. A properly discharged capacitor is safe to handle. Do not skip this step — a 440VAC capacitor can retain enough charge to cause ventricular fibrillation if you contact both terminals simultaneously.
- 3Microfarad (MFD/µF) capacitance test procedure: After safe discharge, disconnect the wires from the capacitor terminals one at a time (photograph the wiring before disconnecting — mixing up HERM and FAN wires causes the compressor or fan to run on the wrong capacitance section). Set your multimeter to capacitance mode (usually indicated by a capacitor symbol or F/µF setting). For a dual-run capacitor: connect probes to HERM and C terminals — this measures the compressor capacitor section. The reading should be within ±6% of the labeled HERM rating (e.g., a 35 µF capacitor should read 32.9–37.1 µF for AHRI ±6% tolerance; within ±10% is often used as the practical field replacement threshold). Then connect probes to FAN and C — should be within ±6% of the FAN rating (typically 5 µF, so 4.7–5.3 µF). Any reading more than 10% below rated value = replace. A reading of 0 µF or OL = capacitor is open, definitely replace.
Get the full fix — Pro members get unlimited AI diagnoses
Save your repair history, get step-by-step AI guidance on any HVAC & cooling issue, and avoid $150+ service call fees.
Try Pro — $7.99/mo- 4Selecting the correct replacement capacitor: Match three values from the old capacitor label: (1) Microfarad ratings — for dual-run, both HERM and FAN values (e.g., 35/5 µF); (2) Voltage rating — use 440VAC rated replacement even if the original was 370VAC, for better transient protection; (3) Pole configuration — a 3-terminal dual-run (HERM/FAN/C) or 2-terminal single-run. Round capacitors (oval cans also exist) — match the terminal configuration. Capacitors are available at HVAC supply houses, electrical supply stores, and online. Using a capacitor with higher voltage rating (440V vs 370V) is correct and preferred. Using a capacitor with different MFD ratings is not acceptable — the HERM and FAN sections must match the compressor and fan motor specifications. A 35/5 µF cannot be substituted with a 40/5 µF for the compressor section without risking motor overheating.
- 5Installation and verification: Reconnect wires to the new capacitor in the same configuration as the original — HERM wire to HERM terminal, FAN wire to FAN terminal, C wire to C terminal. Verify all connections are tight (no loose push-on terminals). Restore power at the disconnect. Set the thermostat to cooling mode and observe startup: the compressor should start within 1–2 seconds of the contactor pulling in, without humming or hesitation. Use a clamp meter on the compressor wire to verify current — it should drop from the brief startup peak to the nameplate RLA (Running Load Amps) within 3–5 seconds. Any sustained hum without compressor starting after capacitor replacement indicates a separate problem (locked rotor compressor, contactor issue, or wiring error). Upload a photo of the new capacitor installation to /diagnose for AI verification before closing the panel.
Save $150+ on a single service call
Less than a cup of coffee — fix it yourself with expert guidance.
- ✓ Step-by-step repair guides with exact part numbers
- ✓ Expert diagnosis in seconds — 500+ problems covered
- ✓ Full tool list & cost estimate before you spend a dime
$150+ service call vs. $7.99/mo · Cancel anytime
Repair vs Replace
A failed run capacitor is the single best-value HVAC DIY repair — the part costs $15–$35, and the repair prevents compressor damage from sustained locked-rotor operation. A compressor that runs without a functioning capacitor draws 3–5× normal amps on every start, overheating the motor windings. Ignoring a failed capacitor can convert a $25 repair into a $1,200–$2,500 compressor replacement within a few weeks. Replace proactively when MFD reading drops below 10% of rated value, even without physical dome. Consider replacing if the unit is over 12–15 years old and the capacitor failure is accompanied by contactor pitting, refrigerant issues, or compressor hard starting — multiple component failures in an aging system may justify unit replacement.
Est. Repair Cost
$15–$35 for a replacement dual-run capacitor (DIY); $100–$200 with an HVAC technician
Est. Replacement Cost
$3,000–$6,500 for a full condenser unit (not warranted for a capacitor failure)
Recommended Tools & Parts
- Buy on Amazon →
Dual Run Capacitor 35/5 MFD 440VAC
Most common residential dual-run capacitor for 2–5 ton split systems. HERM section 35 µF for compressor; FAN section 5 µF for condenser fan. 440VAC rated provides superior transient protection vs 370V. Round 3-terminal (HERM/FAN/C) configuration. Replace if MFD reading is more than 10% below labeled value.
$15–$30
- Buy on Amazon →
Supco SPP6 Hard Start Capacitor Kit
Start capacitor and potential relay kit for residential AC compressors. Reduces startup current draw by 50–70%, protecting the contactor and breaker. Recommended when the compressor has hard-start history or when replacing a run capacitor on a system over 8 years old. Installs in 15 minutes.
$20–$40
- Buy on Amazon →
Fieldpiece SC260 Dual Display Clamp Multimeter
HVAC-specific clamp multimeter with capacitance mode (µF), AC current clamp for RLA verification, and AC/DC voltage. Industry standard for capacitor MFD testing in the field. Auto-ranging. The capacitance function is more accurate than general-purpose multimeters for values above 20 µF.
$80–$130
Links are Amazon affiliate links (tag: fixitfastai-20). Prices are estimates.
Still stuck? Let AI take a look.
Describe your problem or upload a photo — get a diagnosis in seconds.
Related Repairs
A/C Freezing Up
Ice forming on your AC lines or indoor unit? A dirty air filter is the #1 cause — a $10 fix.
Read guide →AC Not Cooling — How to Diagnose Warm Air From Your Vents
AC running but blowing warm air? A dirty filter or blocked condenser are the most common causes — and both are free DIY fixes.
Read guide →Mini Split Not Cooling or Heating — Troubleshooting Ductless AC
Mini split blinking or not cooling? Clean the washable filters first — 40% of ductless AC service calls are solved by this free step.
Read guide →AC Blowing Warm Air: What's Wrong and How to Fix It
AC running but blowing warm or room-temperature air? Thermostat settings, dirty coils, bad capacitor, or low refrigerant are the likely causes.
Read guide →Save $150+ on a single service call
Less than a cup of coffee — fix it yourself with expert guidance.
- ✓ Step-by-step repair guides with exact part numbers
- ✓ Expert diagnosis in seconds — 500+ problems covered
- ✓ Full tool list & cost estimate before you spend a dime
$150+ service call vs. $7.99/mo · Cancel anytime
Still not sure what's wrong?
Get an AI diagnosis in seconds — describe the problem or upload a photo.
Get an AI Diagnosis⚡ Get step-by-step help for YOUR specific appliance
Our AI diagnoses your exact model — not just generic advice. Upload a photo or describe the issue and get a repair plan in seconds.
No account needed for diagnosis. Cancel Pro anytime.
Related Tools
Frequently Asked Questions
- How do I know if my AC capacitor is bad without a multimeter?
- The most reliable physical signs of a failed capacitor: (1) Visible dome or bulge on the top of the cylindrical capacitor can — a flat or slightly concave top is normal; any convex bulge means internal gassing, the capacitor is failed. (2) Oil residue, dark staining, or dried fluid deposits around the capacitor base or terminals — indicates dielectric oil has leaked from a ruptured case. (3) Rust or corrosion on the capacitor terminals suggesting oil has been seeping for an extended period. If you see any of these, the capacitor is failed regardless of any electrical reading. Without a multimeter, you can also observe operational symptoms: compressor hums for a few seconds then shuts off (thermal overload trip), fan starts but compressor doesn't, or breaker trips at startup. These are consistent with capacitor failure but not definitive — a multimeter test is needed to confirm.
- What is the correct MFD tolerance for an AC capacitor — is ±6% or ±10% correct?
- AHRI Standard 730 specifies ±6% tolerance for HVAC run capacitors. This is the engineering standard for capacitors to be within specification. In the field, many HVAC technicians use ±10% as a practical replacement threshold — a capacitor that reads 32 µF on a 35 µF unit (8.6% low) may not cause immediate symptoms but is degraded and should be replaced proactively. A capacitor reading more than 10% below labeled value should always be replaced, and any reading more than 15% below is causing your system symptoms and needs immediate replacement. For the HERM section, being even 10% low significantly reduces compressor start torque — the compressor will run hotter and draw more amps even when it does start successfully.
- What is the difference between a run capacitor and a start capacitor?
- A run capacitor is present on every residential AC unit and remains in the circuit continuously during compressor and condenser fan operation. It is typically a dual-run capacitor (single can with three terminals: HERM, FAN, C) rated 35/5 µF or 45/5 µF at 370 or 440VAC. It improves motor efficiency and provides phase-shift for single-phase motors. A start capacitor (only present on hard-start kit installations like Supco SPP6 or factory-installed hard-start versions) is a high-MFD, short-duty-cycle capacitor (typically 88–108 µF or 161–193 µF) that is only energized for 200–500 milliseconds at startup. A potential relay disconnects the start capacitor once the compressor reaches approximately 75% of operating speed. Start capacitors are physically distinct (usually oval, with two terminals) and fail differently — often open circuit rather than domed. If your system has a hard-start kit, test both capacitors separately.
- Can a swollen capacitor be dangerous to leave in place?
- Yes — a swollen capacitor has built up internal gas pressure from dielectric breakdown and should be replaced immediately. The risks of leaving a domed capacitor in service: (1) The capacitor case can rupture, spraying dielectric oil and potentially causing an arc flash inside the condenser cabinet. (2) A shorted capacitor draws continuous current from the 240VAC supply through a low-resistance path, generating heat that can damage wiring, the contactor, or the control board. (3) The compressor continues to operate without adequate capacitor assistance, drawing excess amps that overheat the compressor motor windings — turning a $25 capacitor repair into a $1,500 compressor job. Turn off the outdoor unit at the disconnect when you discover a domed capacitor and replace it before running the system again.